TY - JOUR
T1 - An Observer-Based Optimal Voltage Control Scheme for Three-Phase UPS Systems
AU - Kim, Eun Kyung
AU - Mwasilu, Francis
AU - Choi, Han Ho
AU - Jung, Jin Woo
N1 - Publisher Copyright:
© 1982-2012 IEEE.
PY - 2015/4
Y1 - 2015/4
N2 - This paper proposes a simple optimal voltage control method for three-phase uninterruptible-power-supply systems. The proposed voltage controller is composed of a feedback control term and a compensating control term. The former term is designed to make the system errors converge to zero, whereas the latter term is applied to compensate for the system uncertainties. Moreover, the optimal load current observer is used to optimize system cost and reliability. Particularly, the closed-loop stability of an observer-based optimal voltage control law is mathematically proven by showing that the whole states of the augmented observer-based control system errors exponentially converge to zero. Unlike previous algorithms, the proposed method can make a tradeoff between control input magnitude and tracking error by simply choosing proper performance indexes. The effectiveness of the proposed controller is validated through simulations on MATLAB/Simulink and experiments on a prototype 600-VA testbed with a TMS320LF28335 DSP. Finally, the comparative results for the proposed scheme and the conventional feedback linearization control scheme are presented to demonstrate that the proposed algorithm achieves an excellent performance such as fast transient response, small steady-state error, and low total harmonic distortion under load step change, unbalanced load, and nonlinear load with the parameter variations.
AB - This paper proposes a simple optimal voltage control method for three-phase uninterruptible-power-supply systems. The proposed voltage controller is composed of a feedback control term and a compensating control term. The former term is designed to make the system errors converge to zero, whereas the latter term is applied to compensate for the system uncertainties. Moreover, the optimal load current observer is used to optimize system cost and reliability. Particularly, the closed-loop stability of an observer-based optimal voltage control law is mathematically proven by showing that the whole states of the augmented observer-based control system errors exponentially converge to zero. Unlike previous algorithms, the proposed method can make a tradeoff between control input magnitude and tracking error by simply choosing proper performance indexes. The effectiveness of the proposed controller is validated through simulations on MATLAB/Simulink and experiments on a prototype 600-VA testbed with a TMS320LF28335 DSP. Finally, the comparative results for the proposed scheme and the conventional feedback linearization control scheme are presented to demonstrate that the proposed algorithm achieves an excellent performance such as fast transient response, small steady-state error, and low total harmonic distortion under load step change, unbalanced load, and nonlinear load with the parameter variations.
KW - Optimal load current observer
KW - optimal voltage control
KW - three-phase inverter
KW - total harmonic distortion (THD)
KW - uninterruptible power supply (UPS)
UR - http://www.scopus.com/inward/record.url?scp=84924898419&partnerID=8YFLogxK
U2 - 10.1109/TIE.2014.2351777
DO - 10.1109/TIE.2014.2351777
M3 - Article
AN - SCOPUS:84924898419
SN - 0278-0046
VL - 62
SP - 2073
EP - 2081
JO - IEEE Transactions on Industrial Electronics
JF - IEEE Transactions on Industrial Electronics
IS - 4
M1 - 6883162
ER -